Classification VI SS 211 according to IEC 62040-3 B. 750 B. 1000 B. 1500 B. 2000 B. 3000
Type rating 750 VA 1000 VA 1500 VA 2000 VA 3000 VA
500 W 700 W 1050 W 1340 W 2100 W
UPS Input
Nominal connection voltage 220 Vac/230 Vac/240 Vac
Voltage range without battery operation 161/184–276 Vac (configurable)
Frequency (automatic detection) 50 Hz/60 Hz
±
5 Hz (> 40 Hz during generator operation)
Current consumption at full load (max.) 5 A 8 A 10 A 10 A 16 A
UPS Output
Rated output voltage/AVR technology 220 Vac/230 Vac/240 Vac
Rated output voltage in battery operation
±
5 %
Frequency in battery operation 50 Hz/60 Hz
±
0.1 Hz
Nominal output current (at 230 Vac) 3.2 A 4.3 A 6.5 A 8.7 A 13.0 A
Changeover time in the event of a mains failure 2–4 ms (typical), 6 ms max.
Voltage curve pure sinusoidal
Overload capacity in mains operation 110 % for 3 min./150 % for 200 ms
Overload protection yes yes yes yes yes
BATTERY
Type sealed, maintenance-free (proprietary brand) - hot swappable (from 1500 VA)
Nominal DC voltage (intermediate circuit) 24 Vdc 48 Vdc 96 Vdc
Autonomy time during nominal load 5 min. 5 min. 5 min. 5 min. 5 min.
- - Expandable via ext. battery modules
Exhaustive discharge protection/protection against excess load yes yes yes yes yes
Charging time (to 90 % of rated capacity) 3 hrs 3 hrs 3 hrs 3 hrs 3 hrs
COMMUNICATION
Interfaces USB and RS232 (with status messages and measured values), communication slot (from 1500 VA)
for SNMP, potential-free relay contacts, input contact for emergency shutdown,
Configuration panel for selecting the voltage and setting the operating mode
Shutdown software (on CD) 5 network licences included in delivery
for all major operating systems (e. g. Windows, Linux, Mac)
Alarms (acoustic/optical) Separate LED bar graphs for UPS capacity utilisation and battery capacity display,
indicators for mains failure, overload, battery discharged, replace battery, fault
GENERAL DATA
Inherent noise (1m distance) < 45 dB(A)
Operating temperature range 0°-35°C
EMC Conformity EN 50091-2, EN 61000-3-2, EN 61000-3-3
EMC emitted interference EN 61000-6-3 Class A
Overvoltage protection for data lines RJ11 (phone, fax, modem)/RJ45 (Ethernet 10 Mbps/100 Mbps)
Relative humidity 0-90 % (without condensation)
Installation height up to 1 000 m at nominal output
Load outputs 4 x IEC 320 C13 6 x IEC 320 C13 8 x IEC 320 C13
removable module 1 x IEC 320 C19
Housing colour Blackline
Dimensions of UPS approx. W x H x D (mm) 235 x 88 x 383 217 x 88 x 414 438 x 88 x 582
Dimensions of battery approx. W x H x D (mm) - - 217 x 88 x 414 438 x 88 x 582
Weight of UPS approx. 8.5 kg 9.5 kg 6.5 kg 31.5 kg
Weight of battery approx. - - 12 kg 40.5 kg
Scope of delivery Mains connection cable, 2 device connecting cables, management software
"CompuWatch" (CD), USB and RS232 communication cables, operating instructions
Conformity CE